IAQ Team Building Maintenance Plan (BMP) Visit Progress - South Lake ES (564) Initial Visit

Kick-Off Meeting: 04/17/07

Walkthrough: 05/08/07

Work Plan Provided to School: 05/17/07 - Download

Supply Ventilation Unit PM (Cleaning; Mechanical Evaluation; Repairs, if needed):

Unit ID
Area/Zone served by Unit
Unit Type*
Cleaned
Mech Eval
Repairs/Notes
564-MainEntrance-E-1 Main entrance
Ceiling Fan Coil Unit
10/08EJC
Re-calibrated thermostat.
564-Principal-A-1 Principal's office
Unit Ventilator
06/13J
10/08EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch.
564-Principal-A-2 Principal's office
Unit Ventilator
06/13J
10/08EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch.
564-Health-C-1 Health room
Wall Heater
06/13LJ
 
564-WorkRoom-A-1 Main office work room
Unit Ventilator
06/12L
10/01EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired electrical wires; installed new electric-pressure switch; installed new freeze-stat.
564-MainOfficeSBR-A-1 Main office staff restroom
Wall Heater
06/13LJ
 
564-MainOfficeSBR-A-2 Main office staff restroom
Wall Heater
06/13LJ
 
564-AssistantPrincipal-A-1 Assistant Principal's office
Unit Ventilator
06/12L
10/04EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch.
564-StaffLounge-A-1 Staff lounge
Unit Ventilator
06/12L
10/02EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired fan motor wires; installed new electric-pressure switch.
564-StaffLounge-A-2 Staff lounge
Unit Ventilator
06/12L
10/03EJC
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired fan motor wires; installed new electric-pressure switch.
564-SBR/APR-C-1 Restroom R-4 by APR
Wall Heater
06/14L
 
564-1-B-1 Room 1, Computer Lab
Unit Ventilator
06/18SK
09/05EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-BBR/1-B-1 Boys' restroom by room 1
Fan Coil Unit
06/19L
 
564-2-B-1 Room 2
Unit Ventilator
06/18QT
09/05EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-3-A-1 Room 3
Unit Ventilator
06/20SK
09/04EJC
Replaced thermostat; adjusted air dampers; installed new on/off and fan speed switch; installed new low-limit control.
564-4-A-1 Room 4
Unit Ventilator
06/20QT
09/04EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-5-D-1 Room 5
Unit Ventilator
08/21L
09/04EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-6-D-1 Room 6
Unit Ventilator
06/21T
09/04EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-7-C-1 Room 7
Unit Ventilator
06/28T
08/27EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-8-D-1 Room 8
Unit Ventilator
06/29S
 
564-9-D-1 Room 9
Unit Ventilator
06/29T
 
564-10-D-1 Room 10
Unit Ventilator
06/21K
 
564-11-D-1 Room 11
Unit Ventilator
07/02SK
08/23EJC
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control.
564-GBR/11-C-1 Girls' restroom by room 11
Wall Heater
06/28SK
 
564-12A-A-1 Room 12A
Unit Ventilator
07/01K
 
564-12B-B-1 Room 12B
Unit Ventilator
07/02T
 
564-HU/12A-E-1 Hall by 12A
Ceiling Fan Coil Unit
06/13QT
 
564-12C-D-1 Room 12C
Unit Ventilator
07/02Q
 
564-HU/12C-E-1 Grade 4 pod entrance
Ceiling Fan Coil Unit
06/13QT
 
564-13A-C-1 Room 13A
Unit Ventilator
07/03S
 
564-13B-B-1 Room 13B
Unit Ventilator
07/03K
 
564-13C-D-1 Room 13C
Unit Ventilator
07/03QT
 
564-14A-E-1 Room 14A, Music
Ceiling Unit Ventilator
07/03QT
 
564-14B-E-1 Room 14B
Ceiling Unit Ventilator
07/09SK
 
564-HU/14B-E-1 Hall by room 14B
Ceiling Fan Coil Unit
06/14L
 
564-14-C-1 Room 14
Unit Ventilator
07/03L
09/05EJC
Replaced thermostat; adjusted air dampers; installed new on/off and fan speed switch; installed new low-limit control.
564-15-C-1 Room 15
Unit Ventilator
07/05K
08/22EJC
Replaced thermostat; adjusted air dampers; installed new low limit; installed new on/off and fan speed switch; installed new low-limit control.
564-16-D-1 Room 16
Unit Ventilator
07/05S
08/15EJC
Replaced thermostat; adjusted air dampers; installed new low limit; installed new on/off and fan speed switch.
564-17-D-1 Room 17
Unit Ventilator
07/05T
 
564-18-A-1 Room 18
Unit Ventilator
07/05Q
08/18EJC
Replaced thermostat; adjusted air dampers; replaced on/off, fan speed switch; installed new low-limit control.
564-19-C-1 Room 19
Unit Ventilator
05/31SKJ
08/02EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-19-C-2 Room 19
Unit Ventilator
05/31SKJ
08/02EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-19-C-3 Room 19
Unit Ventilator
05/31SKJ
08/02EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-19-C-4 Room 19
Unit Ventilator
05/31SKJ
08/02EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-20-B-1 Room 20
Unit Ventilator
06/01K
 
564-20-B-2 Room 20
Unit Ventilator
06/01K
 
564-20-B-3 Room 20
Unit Ventilator
06/04QT
 
564-20-C-1 Room 20
Unit Ventilator
06/04QT
 
564-20-C-2 Room 20
Unit Ventilator
06/04QT
 
564-21-B-1 Room 21
Unit Ventilator
05/31QT
08/08EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-21-B-2 Room 21
Unit Ventilator
05/31QT
08/08EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-21-B-3 Room 21
Unit Ventilator
05/31QT
08/08EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-22-E-1 Rooms 21 and 22
Ceiling Unit Ventilator
06/05QT
08/08EJC
Replaced thermostat; replaced temperature control valve top, spring, and packing.
564-22-B-1 Room 22
Unit Ventilator
06/05QT
08/08EJC
Replaced thermostat. Unit is missing heat-exchange coil.
564-22-B-2 Room 22
Unit Ventilator
06/05QT
08/08EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-22-B-3 Room 22
Unit Ventilator
06/05QT
08/08EJC
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat.
564-23-A-1 Room 23
Unit Ventilator
07/06QK
 
564-23-A-2 Room 23
Unit Ventilator
07/06QK
 
564-23-B-1 Room 23
Unit Ventilator
07/06QK
 
564-23-B-2 Room 23
Unit Ventilator
06/12Q
 
564-23-B-3 Room 23
Unit Ventilator
06/12Q
 
564-24-A-1 Room 24
Unit Ventilator
06/08QK
 
564-24-A-2 Room 24
Unit Ventilator
06/07K
 
564-24-A-3 Room 24
Unit Ventilator
06/07K
 
564-24-A-4 Room 24
Unit Ventilator
06/08QK
 
564-24B-A-1 Room 24B, SPT
Unit Ventilator
06/12T
09/06EJC
Replaced thermostat; replaced temperature-control valve top and spring kit; replaced pneumatic lines from valve to thermostat; installed new electric-pressure and on/off switch.
564-24B-D-1 Room 24, SPT
Unit Ventilator
06/12T
09/06EJC
Replaced thermostat; replaced temperature-control valve top and spring kit; replaced pneumatic lines from valve to thermostat.
564-HU/24-E-1 Hall by room 24
Ceiling Fan Coil Unit
06/13SK
10/08EJC
Re-calibrated thermostat; replaced valve spring assembly.
564-HU/APR-B-1 Hall by All-Purpose Room
Fan Coil Unit
06/14SK
10/05EJC
Replaced thermostat; replaced control valve top and spring assembly; installed new pneumatic lines to thermostat.
564-Kitchen-E-1 Kitchen
Ceiling Fan Coil Unit
07/09QT
 
564-HU/BSM-E-1 Hall by BSM office
Ceiling Fan Coil Unit
06/13SK
10/08EJC
Re-calibrated thermostat; replaced valve spring assembly.
564-29-C-1 Rooms 29 and K-1
Unit Ventilator
06/12SK
08/15EJC
Replaced thermostat; installed new on/off and fan speed switch; adjusted air dampers; replaced low limit.
564-BR/K1-E-1 Room K1
Ceiling Unit Ventilator
07/09QT
08/15EJC
Replaced thermostat; replaced air station.
564-BR/K1-D-1 K1 restroom
Wall Heater
06/18L
08/15EJC
 
564-BR/K1-D-2 K1 restroom
Fan Coil Unit
08/15EJC
Replaced thermostat; new air station.
564-BR/K2-E-1 K2 hall
Ceiling Fan Coil Unit
06/14SK
 
564-K2-C-1 Rooms K2 and 29
Unit Ventilator
06/12SK
08/14EJC
Replaced thermostat; adjusted air dampers; replaced air restrictor; replaced low limit.
564-BR/K2-B-1 K2 restroom
Wall Heater
06/15L
08/15EJC
 
564-AHU7/K3 Room K3
Heat Pump
07/13S
 
564-AHU6/K4 Room K4
Heat Pump
07/13S
 
564-AHU8/K5 Room K5
Heat Pump
07/13Q
 
564-HU/K5-E-1 Hall by K5
Ceiling Fan Coil Unit
06/14L
 
564-AHU9/K6 Room K6
Heat Pump
07/13Q
 
564-AHU5/30 Room 30
Heat Pump
07/13T
 
564-AHU11/31 Room 31
Heat Pump
07/13T
 
564-AHU10/32 Room 32
Heat Pump
07/13T
 
564-AHU12/33 Room 33, Art
Heat Pump
07/10QTL
 
564-HU/Gym-E-1 Hall by gym
Ceiling Fan Coil Unit
06/14QT
 
564-AHU14/34 Room 34
Heat Pump
07/13T
 
564-AHU13/35 Room 35
Heat Pump
07/10QTL
 
564-AHU16/36 Room 36
Heat Pump
07/13Q
 
564-AHU15/37 Room 37, ESOL
Heat Pump
07/13S
 
564-HU/37-E-1 Hall by north entrance (by 37)
Ceiling Fan Coil Unit
06/14QT
 
564-38A-E-1 Gym office, 38A
Ceiling Unit Ventilator
07/09SK
 
564-AHU18/40 Room 40
Heat Pump
07/20Q
 
564-HU/40-E-1 Stairwell by 40
Ceiling Fan Coil Unit
08/21S
 
564-AHU17/41 Room 41
Heat Pump
07/20Q
 
564-AHU20/42 Room 42
Heat Pump
07/20Q
 
564-AHU19/43 Room 43
Heat Pump
07/20Q
 
564-HU/43-E-1 Hall by 43
Ceiling Fan Coil Unit
08/21S
 
564-44A-D-1 Room 44A, Server Room
Split-Ductless Air Conditioner
08/21S
 
   
 
564-MechLoft-C-1 Mechanical Loft
Fan Coil Unit
07/08L
10/08EJC
Replaced thermostat.
564-MechLoft-AHU1 IMC
AHU
07/18LJ
08/22EJC
Replaced thermostat; adjusted air dampers.
564-MechLoft-AHU2 All-Purpose Room
AHU
07/18SK
10/08EJC
Thermostat is controlled by energy management system.
564-MechLoft-AHU4 Kitchen
AHU (heat only)
07/16LJ
10/08EJC
Thermostat is controlled by energy management system.
564-AHU3 Southwest classrooms, offices
AHU
07/18QT
 
* AHU: central air handling unit; Ceiling Unit Ventilator: ceiling-mounted ventilation unit; Unit Ventilator: wall-mounted ventilation unit; Ceiling Fan Coil Unit: ceiling-mounted ventilation unit (does not supply outdoor air); Fan Coil Unit: wall-mounted ventilation unit (does not supply outdoor air); RTU: rooftop air handler; VAV box: variable-air volume box (duct-mounted device that controls room temperatures by modulating airflow); Reheat Coil: duct-mounted device that provides supplemental heat. VAV boxes and reheat coils typically do not require cleaning; Heat Pump: Heat pump or refrigerant air-conditioner with electric heat.

 

Exhaust Fan PM (Mechanical Evaluation; Repairs, if needed):

Fan No.
Area/Zone served by Unit
Unit Type
Mech Eval
Repairs
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
   
 
 
 

 

Air Station PM:

 

Follow-Up Walkthrough:

 

Exit Meeting (Presentation of Site Visit Report and Building Maintenance Plan):

 

 

Notes:
Recommended installation of exhaust fan for IMC workroom to reduce heat, ozone to Environmental Safety
Coordinator Yarup.
 
 
 

 

 

 

Updated May 9, 2011 | Maintained by Division of Maintenance ITSS