IAQ Team Building Maintenance Plan (BMP) Visit Progress - South Lake ES (564) Initial Visit
Unit ID |
Area/Zone served by Unit |
Unit Type* |
Cleaned |
Mech Eval |
Repairs/Notes |
| 564-MainEntrance-E-1 |
Main entrance |
Ceiling Fan Coil Unit |
|
10/08EJC |
Re-calibrated thermostat. |
| 564-Principal-A-1 |
Principal's office |
Unit Ventilator |
06/13J |
10/08EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch. |
| 564-Principal-A-2 |
Principal's office |
Unit Ventilator |
06/13J |
10/08EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch. |
| 564-Health-C-1 |
Health room |
Wall Heater |
06/13LJ |
|
|
| 564-WorkRoom-A-1 |
Main office work room |
Unit Ventilator |
06/12L |
10/01EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired electrical wires; installed new electric-pressure switch; installed new freeze-stat. |
| 564-MainOfficeSBR-A-1 |
Main office staff restroom |
Wall Heater |
06/13LJ |
|
|
| 564-MainOfficeSBR-A-2 |
Main office staff restroom |
Wall Heater |
06/13LJ |
|
|
| 564-AssistantPrincipal-A-1 |
Assistant Principal's office |
Unit Ventilator |
06/12L |
10/04EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; installed new electric-pressure switch. |
| 564-StaffLounge-A-1 |
Staff lounge |
Unit Ventilator |
06/12L |
10/02EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired fan motor wires; installed new electric-pressure switch. |
| 564-StaffLounge-A-2 |
Staff lounge |
Unit Ventilator |
06/12L |
10/03EJC |
Replaced thermostat; replaced water control valve top and spring assembly; adjusted air dampers; installed new pneumatic lines; repaired fan motor wires; installed new electric-pressure switch. |
| 564-SBR/APR-C-1 |
Restroom R-4 by APR |
Wall Heater |
06/14L |
|
|
| 564-1-B-1 |
Room 1, Computer Lab |
Unit Ventilator |
06/18SK |
09/05EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-BBR/1-B-1 |
Boys' restroom by room 1 |
Fan Coil Unit |
06/19L |
|
|
| 564-2-B-1 |
Room 2 |
Unit Ventilator |
06/18QT |
09/05EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-3-A-1 |
Room 3 |
Unit Ventilator |
06/20SK |
09/04EJC |
Replaced thermostat; adjusted air dampers; installed new on/off and fan speed switch; installed new low-limit control. |
| 564-4-A-1 |
Room 4 |
Unit Ventilator |
06/20QT |
09/04EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-5-D-1 |
Room 5 |
Unit Ventilator |
08/21L |
09/04EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-6-D-1 |
Room 6 |
Unit Ventilator |
06/21T |
09/04EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-7-C-1 |
Room 7 |
Unit Ventilator |
06/28T |
08/27EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-8-D-1 |
Room 8 |
Unit Ventilator |
06/29S |
|
|
| 564-9-D-1 |
Room 9 |
Unit Ventilator |
06/29T |
|
|
| 564-10-D-1 |
Room 10 |
Unit Ventilator |
06/21K |
|
|
| 564-11-D-1 |
Room 11 |
Unit Ventilator |
07/02SK |
08/23EJC |
Replaced thermostat; adjusted air dampers; installed new on/off, fan speed switch; installed new low-limit control. |
| 564-GBR/11-C-1 |
Girls' restroom by room 11 |
Wall Heater |
06/28SK |
|
|
| 564-12A-A-1 |
Room 12A |
Unit Ventilator |
07/01K |
|
|
| 564-12B-B-1 |
Room 12B |
Unit Ventilator |
07/02T |
|
|
| 564-HU/12A-E-1 |
Hall by 12A |
Ceiling Fan Coil Unit |
06/13QT |
|
|
| 564-12C-D-1 |
Room 12C |
Unit Ventilator |
07/02Q |
|
|
| 564-HU/12C-E-1 |
Grade 4 pod entrance |
Ceiling Fan Coil Unit |
06/13QT |
|
|
| 564-13A-C-1 |
Room 13A |
Unit Ventilator |
07/03S |
|
|
| 564-13B-B-1 |
Room 13B |
Unit Ventilator |
07/03K |
|
|
| 564-13C-D-1 |
Room 13C |
Unit Ventilator |
07/03QT |
|
|
| 564-14A-E-1 |
Room 14A, Music |
Ceiling Unit Ventilator |
07/03QT |
|
|
| 564-14B-E-1 |
Room 14B |
Ceiling Unit Ventilator |
07/09SK |
|
|
| 564-HU/14B-E-1 |
Hall by room 14B |
Ceiling Fan Coil Unit |
06/14L |
|
|
| 564-14-C-1 |
Room 14 |
Unit Ventilator |
07/03L |
09/05EJC |
Replaced thermostat; adjusted air dampers; installed new on/off and fan speed switch; installed new low-limit control. |
| 564-15-C-1 |
Room 15 |
Unit Ventilator |
07/05K |
08/22EJC |
Replaced thermostat; adjusted air dampers; installed new low limit; installed new on/off and fan speed switch; installed new low-limit control. |
| 564-16-D-1 |
Room 16 |
Unit Ventilator |
07/05S |
08/15EJC |
Replaced thermostat; adjusted air dampers; installed new low limit; installed new on/off and fan speed switch. |
| 564-17-D-1 |
Room 17 |
Unit Ventilator |
07/05T |
|
|
| 564-18-A-1 |
Room 18 |
Unit Ventilator |
07/05Q |
08/18EJC |
Replaced thermostat; adjusted air dampers; replaced on/off, fan speed switch; installed new low-limit control. |
| 564-19-C-1 |
Room 19 |
Unit Ventilator |
05/31SKJ |
08/02EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-19-C-2 |
Room 19 |
Unit Ventilator |
05/31SKJ |
08/02EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-19-C-3 |
Room 19 |
Unit Ventilator |
05/31SKJ |
08/02EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-19-C-4 |
Room 19 |
Unit Ventilator |
05/31SKJ |
08/02EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-20-B-1 |
Room 20 |
Unit Ventilator |
06/01K |
|
|
| 564-20-B-2 |
Room 20 |
Unit Ventilator |
06/01K |
|
|
| 564-20-B-3 |
Room 20 |
Unit Ventilator |
06/04QT |
|
|
| 564-20-C-1 |
Room 20 |
Unit Ventilator |
06/04QT |
|
|
| 564-20-C-2 |
Room 20 |
Unit Ventilator |
06/04QT |
|
|
| 564-21-B-1 |
Room 21 |
Unit Ventilator |
05/31QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-21-B-2 |
Room 21 |
Unit Ventilator |
05/31QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-21-B-3 |
Room 21 |
Unit Ventilator |
05/31QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-22-E-1 |
Rooms 21 and 22 |
Ceiling Unit Ventilator |
06/05QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top, spring, and packing. |
| 564-22-B-1 |
Room 22 |
Unit Ventilator |
06/05QT |
08/08EJC |
Replaced thermostat. Unit is missing heat-exchange coil. |
| 564-22-B-2 |
Room 22 |
Unit Ventilator |
06/05QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-22-B-3 |
Room 22 |
Unit Ventilator |
06/05QT |
08/08EJC |
Replaced thermostat; replaced temperature control valve top and spring; adjusted air dampers; replaced pneumatic lines to unit from thermostat; replaced EP switch and freezestat. |
| 564-23-A-1 |
Room 23 |
Unit Ventilator |
07/06QK |
|
|
| 564-23-A-2 |
Room 23 |
Unit Ventilator |
07/06QK |
|
|
| 564-23-B-1 |
Room 23 |
Unit Ventilator |
07/06QK |
|
|
| 564-23-B-2 |
Room 23 |
Unit Ventilator |
06/12Q |
|
|
| 564-23-B-3 |
Room 23 |
Unit Ventilator |
06/12Q |
|
|
| 564-24-A-1 |
Room 24 |
Unit Ventilator |
06/08QK |
|
|
| 564-24-A-2 |
Room 24 |
Unit Ventilator |
06/07K |
|
|
| 564-24-A-3 |
Room 24 |
Unit Ventilator |
06/07K |
|
|
| 564-24-A-4 |
Room 24 |
Unit Ventilator |
06/08QK |
|
|
| 564-24B-A-1 |
Room 24B, SPT |
Unit Ventilator |
06/12T |
09/06EJC |
Replaced thermostat; replaced temperature-control valve top and spring kit; replaced pneumatic lines from valve to thermostat; installed new electric-pressure and on/off switch. |
| 564-24B-D-1 |
Room 24, SPT |
Unit Ventilator |
06/12T |
09/06EJC |
Replaced thermostat; replaced temperature-control valve top and spring kit; replaced pneumatic lines from valve to thermostat. |
| 564-HU/24-E-1 |
Hall by room 24 |
Ceiling Fan Coil Unit |
06/13SK |
10/08EJC |
Re-calibrated thermostat; replaced valve spring assembly. |
| 564-HU/APR-B-1 |
Hall by All-Purpose Room |
Fan Coil Unit |
06/14SK |
10/05EJC |
Replaced thermostat; replaced control valve top and spring assembly; installed new pneumatic lines to thermostat. |
| 564-Kitchen-E-1 |
Kitchen |
Ceiling Fan Coil Unit |
07/09QT |
|
|
| 564-HU/BSM-E-1 |
Hall by BSM office |
Ceiling Fan Coil Unit |
06/13SK |
10/08EJC |
Re-calibrated thermostat; replaced valve spring assembly. |
| 564-29-C-1 |
Rooms 29 and K-1 |
Unit Ventilator |
06/12SK |
08/15EJC |
Replaced thermostat; installed new on/off and fan speed switch; adjusted air dampers; replaced low limit. |
| 564-BR/K1-E-1 |
Room K1 |
Ceiling Unit Ventilator |
07/09QT |
08/15EJC |
Replaced thermostat; replaced air station. |
| 564-BR/K1-D-1 |
K1 restroom |
Wall Heater |
06/18L |
08/15EJC |
|
| 564-BR/K1-D-2 |
K1 restroom |
Fan Coil Unit |
|
08/15EJC |
Replaced thermostat; new air station. |
| 564-BR/K2-E-1 |
K2 hall |
Ceiling Fan Coil Unit |
06/14SK |
|
|
| 564-K2-C-1 |
Rooms K2 and 29 |
Unit Ventilator |
06/12SK |
08/14EJC |
Replaced thermostat; adjusted air dampers; replaced air restrictor; replaced low limit. |
| 564-BR/K2-B-1 |
K2 restroom |
Wall Heater |
06/15L |
08/15EJC |
|
| 564-AHU7/K3 |
Room K3 |
Heat Pump |
07/13S |
|
|
| 564-AHU6/K4 |
Room K4 |
Heat Pump |
07/13S |
|
|
| 564-AHU8/K5 |
Room K5 |
Heat Pump |
07/13Q |
|
|
| 564-HU/K5-E-1 |
Hall by K5 |
Ceiling Fan Coil Unit |
06/14L |
|
|
| 564-AHU9/K6 |
Room K6 |
Heat Pump |
07/13Q |
|
|
| 564-AHU5/30 |
Room 30 |
Heat Pump |
07/13T |
|
|
| 564-AHU11/31 |
Room 31 |
Heat Pump |
07/13T |
|
|
| 564-AHU10/32 |
Room 32 |
Heat Pump |
07/13T |
|
|
| 564-AHU12/33 |
Room 33, Art |
Heat Pump |
07/10QTL |
|
|
| 564-HU/Gym-E-1 |
Hall by gym |
Ceiling Fan Coil Unit |
06/14QT |
|
|
| 564-AHU14/34 |
Room 34 |
Heat Pump |
07/13T |
|
|
| 564-AHU13/35 |
Room 35 |
Heat Pump |
07/10QTL |
|
|
| 564-AHU16/36 |
Room 36 |
Heat Pump |
07/13Q |
|
|
| 564-AHU15/37 |
Room 37, ESOL |
Heat Pump |
07/13S |
|
|
| 564-HU/37-E-1 |
Hall by north entrance (by 37) |
Ceiling Fan Coil Unit |
06/14QT |
|
|
| 564-38A-E-1 |
Gym office, 38A |
Ceiling Unit Ventilator |
07/09SK |
|
|
| 564-AHU18/40 |
Room 40 |
Heat Pump |
07/20Q |
|
|
| 564-HU/40-E-1 |
Stairwell by 40 |
Ceiling Fan Coil Unit |
08/21S |
|
|
| 564-AHU17/41 |
Room 41 |
Heat Pump |
07/20Q |
|
|
| 564-AHU20/42 |
Room 42 |
Heat Pump |
07/20Q |
|
|
| 564-AHU19/43 |
Room 43 |
Heat Pump |
07/20Q |
|
|
| 564-HU/43-E-1 |
Hall by 43 |
Ceiling Fan Coil Unit |
08/21S |
|
|
| 564-44A-D-1 |
Room 44A, Server Room |
Split-Ductless Air Conditioner |
08/21S |
|
|
| |
|
|
|
|
|
| 564-MechLoft-C-1 |
Mechanical Loft |
Fan Coil Unit |
07/08L |
10/08EJC |
Replaced thermostat. |
| 564-MechLoft-AHU1 |
IMC |
AHU |
07/18LJ |
08/22EJC |
Replaced thermostat; adjusted air dampers. |
| 564-MechLoft-AHU2 |
All-Purpose Room |
AHU |
07/18SK |
10/08EJC |
Thermostat is controlled by energy management system. |
| 564-MechLoft-AHU4 |
Kitchen |
AHU (heat only) |
07/16LJ |
10/08EJC |
Thermostat is controlled by energy management system. |
| 564-AHU3 |
Southwest classrooms, offices |
AHU |
07/18QT |
|
|
* AHU: central air handling unit; Ceiling Unit Ventilator: ceiling-mounted ventilation unit; Unit Ventilator: wall-mounted ventilation unit; Ceiling Fan Coil Unit: ceiling-mounted ventilation unit (does not supply outdoor air); Fan Coil Unit: wall-mounted ventilation unit (does not supply outdoor air); RTU: rooftop air handler; VAV box: variable-air volume box (duct-mounted device that controls room temperatures by modulating airflow); Reheat Coil: duct-mounted device that provides supplemental heat. VAV boxes and reheat coils typically do not require cleaning; Heat Pump: Heat pump or refrigerant air-conditioner with electric heat. |