IAQ Team Building Maintenance Plan (BMP) Visit Progress - Montgomery Knolls ES (776) Initial Visit
Unit ID |
Area/Zone served by Unit |
Unit Type* |
Cleaned |
Mech Eval |
Repairs/Notes |
| 776-MainOffice-RTU1 |
Main office suite |
RTU |
07/08T |
07/05EJC |
|
| 776-HU/MainOffice-B-1 |
Hall by main office |
Fan Coil Unit |
04/30S |
07/09EJC |
Replaced thermostat. |
| 776-Comp-RTU2 |
Computer lab (Tech Center) |
RTU |
05/07S |
07/05EJC |
|
| 776-IMC-RTU3 |
IMC, IMC workroom, PEP 10, PEP Suite, Spec Ed 9, Control Room |
RTU |
05/08L |
07/05EJC |
|
| 776-Garden-RTU5 |
IMC garden |
RTU |
05/08S |
07/05EJC |
Replaced fan motor belt. |
| 776-1-B-1 |
Room 1 |
Unit Ventilator |
05/03QK |
05/10EJC |
Re-calibrated thermostat. |
| 776-HU/1-A-1 |
Hall by 1 |
Fan Coil Unit |
04/30K |
07/09EJC |
Replaced thermostat. |
| 776-2-B-1 |
Room 2 |
Unit Ventilator |
05/03QK |
05/10EJC |
Re-calibrated thermostat; re-packed valve, installed new water valve top and spring; adjusted air dampers. |
| 776-3-B-1 |
Room 3 |
Unit Ventilator |
04/27K |
05/10EJC |
Re-calibrated thermostat. |
| 776-4-B-1 |
Room 4 |
Unit Ventilator |
04/27S |
05/10EJC |
Re-calibrated thermostat. |
| 776-5-B-1 |
Room 5 |
Unit Ventilator |
04/26J |
05/15EJC |
Re-calibrated thermostat; re-packed valve, installed new water valve top and spring. |
| 776-6-C-1 |
Room 6 |
Unit Ventilator |
04/24K |
05/16EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-HU/6-E-1 |
Hall by 6 |
Ceiling Fan Coil Unit |
05/15J |
06/21EJC |
Re-opened water valve to heat-exchange coil - valve was closed. |
| 776-7-RTU4 |
Room 7 |
RTU |
05/07J |
07/05EJC |
Replaced fan belt. |
| 776-SpeechTherapy-C-1 |
PEP suite, Speech Therapy |
Unit Ventilator |
04/30L |
05/16EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-10PT-C-1 |
10 Physical Therapy |
Unit Ventilator |
04/26K |
05/16EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-10PT-C-2 |
10 Physical Therapy |
Unit Ventilator |
04/26S |
05/23EJC |
Re-calibrated thermostat; replaced water valve components; oiled air dampers. |
| 776-10-C-1 |
10 PEP |
Unit Ventilator |
04/26T |
05/23EJC |
Replaced thermostat; replaced water valve components; oiled air dampers; repaired broken pneumatic line inside wall. |
| 776-11-A-1 |
Room 11 |
Unit Ventilator |
04/27Q |
06/06EJC |
Recalibrated thermostat; replaced water valve top, spring assembly, and packing. |
| 776-11-A-2 |
Room 11 |
Unit Ventilator |
04/27T |
06/06EJC |
Re-calibrated thermostat. |
| 776-12-C-1 |
Room 12 |
Unit Ventilator |
04/24J |
05/24EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-13-A-1 |
Room 13 |
Unit Ventilator |
04/22S |
06/06EJC |
Replaced thermostat. |
| 776-13-A-2 |
Room 13 |
Unit Ventilator |
04/24L |
06/06EJC |
Replaced thermostat. |
| 776-13Storage-A-1 |
Room 13 storage |
Fan Coil Unit |
10/15QT |
07/12EJC |
Re-calibrated thermostat. |
| 776-14-C-1 |
Room 14 |
Unit Ventilator |
04/23S |
05/24EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-14-D-1 |
Room 14 |
Fan Coil Unit |
04/24K |
05/24EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-15-A-1 |
Room 15 |
Unit Ventilator |
04/23J |
06/06EJC |
Replaced thermostat; replaced damaged fan assembly; replaced water valve top, spring kit, and packing. |
| 776-15-A-2 |
Room 15 |
Unit Ventilator |
04/23L |
06/06EJC |
Replaced thermostat. |
| 776-16-B-1 |
Room 16 |
Fan Coil Unit |
04/23Q |
05/24EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-16-C-1 |
Room 16 |
Unit Ventilator |
04/23T |
05/24EJC |
Re-calibrated thermostat; replaced water valve top; oiled air dampers. |
| 776-17-A-1 |
Room 17 |
Unit Ventilator |
04/20K |
06/05EJC |
Recalibrated thermostat; replaced water valve top, spring kit, and packing; adjusted air dampers. |
| 776-HU/17-E-1 |
Hall by 17 |
Ceiling Fan Coil Unit |
04/30J |
06/12EJC |
Replaced thermostat. |
| 776-18-D-1 |
Room 18 |
Fan Coil Unit |
04/20T |
05/25EJC |
Re-calibrated thermostat; replaced water valve components; oiled air dampers. |
| 776-18-C-1 |
Room 18 |
Unit Ventilator |
04/20Q |
05/25EJC |
Replaced thermostat; oiled air dampers; fabricated and installed new condensate drain pan. |
| 776-19-A-1 |
Room 19 |
Unit Ventilator |
10/15QT |
|
|
| 776-20-C-1 |
Room 20 |
Unit Ventilator |
04/20J |
05/29EJC |
Re-calibrated thermostat; replaced water valve components; oiled air dampers. |
| 776-20-B-1 |
Room 20 |
Unit Ventilator |
04/20L |
05/29EJC |
Re-calibrated thermostat; oiled air dampers. |
| 776-21-C-1 |
21 Music |
Unit Ventilator |
04/19S |
06/05EJC |
Re-calibrated thermostat. |
| 776-21-C-2 |
21 Music |
Unit Ventilator |
04/19Q |
07/09EJC |
Re-calibrated thermostat; replaced fan motor; adjusted air dampers. |
| 776-21Storage-C-1 |
21 Music Storage |
Unit Ventilator |
04/19K |
06/22EJC |
Replaced thermostat; replaced water valve top, spring kit, and packing. |
| 776-GenStorage-A-1 |
Storage room across 21 |
Unit Ventilator |
04/19T |
06/05EJC |
Re-calibrated thermostat; replaced water valve top, spring kit, and packing. |
| 776-MPR-AHU1 |
MPR |
AHU |
10/15QT |
10/12EJC |
|
| 776-P.E.Office-C-1 |
P.E. office |
Unit Ventilator |
07/09T |
07/09EJC |
Re-calibrated thermostat; replaced water valve top, spring kit, and packing; adjusted air dampers. |
| 776-HU/MPR-E-1 |
Hall by MPR |
Ceiling Fan Coil Unit |
04/30QT |
06/04EJC |
Thermostat recalibrated. |
| 776-HU/MPR-E-2 |
Hall by MPR |
Ceiling Fan Coil Unit |
04/30QT |
05/31EJC |
Wired unit to building - unit was not wired when installed; opened water shutoff valves. |
| 776-HU/MPR-E-3 |
Hall by MPR |
Ceiling Fan Coil Unit |
04/30QT |
05/30EJC |
Opened water shutoff valves. |
| 776-DryStorage-E-1 |
Kitchen Dry Storage |
Ceiling Fan Coil Unit |
05/09LJ |
10/12EJC |
|
| 776-BSM-D-1 |
BSM office |
Unit Ventilator |
04/18T |
06/04EJC |
Replaced thermostat; replaced water valve top, spring kit, and packing. |
| 776-StaffLounge-A-1 |
Staff lounge |
Unit Ventilator |
04/18J |
05/30EJC |
Replaced thermostat; adjusted water valve spring; oiled air dampers; replaced broken pneumatic line for thermostat. |
| 776-StaffLounge-D-1 |
Staff lounge |
Fan Coil Unit |
04/18L |
05/31EJC |
Replaced thermostat; replaced water valve spring. |
| 776-HU/23A-E-1 |
Hall by staff lounge |
Ceiling Fan Coil Unit |
05/15L |
06/04EJC |
Replaced thermostat; replaced water valve top, spring kit, and packing. |
| 776-24-A-1 |
Room 24 |
Unit Ventilator |
04/18Q |
06/07EJC |
Re-calibrated thermostat. |
| 776-25-C-1 |
25 Linkages, back room |
Unit Ventilator |
04/19J |
06/18EJC |
Re-calibrated thermostat; replaced water valve top, spring, packing; adjusted air dampers; repaired pneumatic line to unit. |
| 776-26-A-1 |
Room 26 |
Unit Ventilator |
04/18K |
06/25EJC |
Re-calibrated thermostat; replaced water valve top, spring kit, and packing; adjusted air dampers. |
| 776-27-C-1 |
Room 27 |
Unit Ventilator |
04/17J |
06/26EJC |
Re-calibrated thermostat. |
| 776-28-A-1 |
Room 28 |
Unit Ventilator |
04/17Q |
06/26EJC |
Re-calibrated thermostat; replaced water valve top, spring kit, and packing. |
| 776-29-C-1 |
Room 29 |
Unit Ventilator |
04/17T |
06/26EJC |
Replaced thermostat; replaced water valve top, spring kit, and packing. |
| 776-30-A-1 |
Room 30 |
Unit Ventilator |
04/17S |
06/27EJC |
Re-calibrated thermostat. |
| 776-31-C-1 |
Room 31 |
Unit Ventilator |
04/17K |
06/27EJC |
Re-calibrated thermostat; replaced water valve top, spring kit, and packing. |
| 776-32-A-1 |
Room 32 |
Unit Ventilator |
04/17L |
06/27EJC |
Re-calibrated thermostat. |
| 776-33-C-1 |
Room 33 |
Unit Ventilator |
04/19L |
06/27EJC |
Replaced thermostat; replaced water valve top, spring kit, and packing. |
| 776-ML700-A-1 |
Portable ML700 Even Start |
Heat Pump |
05/04J |
07/12EJC |
Adjusted air damper. |
| 776-MO146-D-1 |
Portable MO146 ESOL |
Heat Pump |
05/01K |
07/12EJC |
|
| 776-MO146-D-2 |
Portable MO146 ESOL |
Heat Pump |
05/01S |
07/12EJC |
|
| 776-ML451-D-1 |
Portable ML451 Cochran |
Heat Pump |
05/02L |
07/12EJC |
Associated exhaust fan only operates during cooling mode. |
| 776-ML296-B-1 |
Portable ML296 Stroud |
Heat Pump |
05/02L |
07/12EJC |
Replaced exhaust fan motor. |
| 776-ML509-C-1 |
Portable ML509 Watts |
Heat Pump |
05/01T |
07/06EJC |
Associated exhaust fan only operates during cooling mode. |
| 776-ML429-A-1 |
Portable ML429 Pak |
Heat Pump |
05/01Q |
07/06EJC |
|
| 776-ML430-A-1 |
Portable ML430 Jones |
Heat Pump |
05/02T |
07/06EJC |
|
| 776-ML428-A-1 |
Portable ML428 Brophy |
Heat Pump |
05/02K |
07/06EJC |
|
* AHU: central air handling unit; Ceiling Unit Ventilator: ceiling-mounted ventilation unit; Unit Ventilator: wall-mounted ventilation unit; Ceiling Fan Coil Unit: ceiling-mounted ventilation unit (does not supply outdoor air); Fan Coil Unit: wall-mounted ventilation unit (does not supply outdoor air); RTU: rooftop air handler; VAV box: variable-air volume box (duct-mounted device that controls room temperatures by modulating airflow); Reheat Coil: duct-mounted device that provides supplemental heat. VAV boxes and reheat coils typically do not require cleaning; Heat Pump: Heat pump or refrigerant air-conditioner with electric heat. |