IAQ Team Building Maintenance Plan (BMP) Visit Progress - Matsunaga/Longview Initial Visit
Kick-Off Meeting: Completed
Walkthrough: Initial Walkthrough Completed
Work Plan Provided to School: 08/20/07 - Download
Supply Ventilation Unit PM (Cleaning; Mechanical Evaluation; Repairs, if needed):
Matsunaga Elementary School |
Unit ID |
Area/Zone served by Unit |
Unit Type* |
Cleaned |
Mech Eval |
Repairs/Notes |
| 523-ML610-A-1 |
Portable ML610 |
Heat Pump |
08/27 |
|
|
| 523-ML583-C-1 |
Portable ML583 |
Heat Pump |
08/27S |
|
|
| 523-ML582-A-1 |
Portable ML582 |
Heat Pump |
08/21K |
|
|
| 523-ML581-D-1 |
Portable ML581 |
Heat Pump |
09/17J |
|
|
| 523-ML580-C-1 |
Portable ML580 |
Heat Pump |
08/28L |
|
|
| 523-ML579-C-1 |
Portable ML579 |
Heat Pump |
08/27L |
|
|
| 523-ML578-C-1 |
Portable ML578 |
Heat Pump |
09/17L |
|
|
| 523-ML677-D-1 |
Portable ML677 |
Heat Pump |
08/27 |
|
|
| 523-ML678-C-1 |
Portable ML678 |
Heat Pump |
08/24 |
|
|
| 523-ML679-C-1 |
Portable ML679 |
Heat Pump |
08/27J |
|
|
| 523-ML680-A-1 |
Portable ML680 |
Heat Pump |
08/24L |
|
|
| 523-ML681-C-1 |
Portable ML681 |
Heat Pump |
08/24J |
|
|
| 523-100-E-1 |
Main office (Matsunaga) |
Ceiling Heat Pump |
09/19L |
|
|
| 523-100-E-2 |
Main office (Matsunaga), 100P |
Ceiling Heat Pump |
09/17J |
|
|
| 523-100A-E-1 |
Principal's office |
Ceiling Heat Pump |
09/17J |
|
|
| 523-100B-E-1 |
100B Conference room |
Ceiling Heat Pump |
09/19L |
|
|
| 523-100H-E-1 |
100H Work room |
Ceiling Heat Pump |
09/19L |
|
|
| 523-HU/100C-E-1 |
100C, 100D Offices |
Ceiling Heat Pump |
09/19L |
|
|
| 523-100K-E-1 |
Hall outside main office |
Ceiling Heat Pump |
09/17J |
|
|
| 523-100K-E-2 |
100K Health, 100L Office |
Ceiling Heat Pump |
09/21T |
|
|
| 523-101Office-E-1 |
101 Gym office |
Ceiling Heat Pump |
09/14Q |
|
|
| 523-HVU1 |
101 Gym |
HVU |
09/06Q |
|
|
| 523-102-E-1 |
102 IMC (Matsunaga) |
Ceiling Heat Pump |
09/19J |
|
|
| 523-102-E-2 |
102 IMC (Matsunaga) |
Ceiling Heat Pump |
|
|
|
| 523-102C-E-1 |
102C Storage, 102B Work room, IMC office, IMC server room, 102F Studio |
Ceiling Heat Pump |
09/19J |
|
|
| 523-102I-E-1 |
102I Computer lab |
Ceiling Heat Pump |
09/19KS |
|
|
| 523-103-E-1 |
103, adjacent hall (Main Level) |
Ceiling Heat Pump |
09/19J |
|
|
| 523-104-E-1 |
104 (Main Level) |
Ceiling Heat Pump |
09/21L |
|
|
| 523-105-E-1 |
105, adjacent hall (Main Level) |
Ceiling Heat Pump |
09/20L |
|
|
| 523-105A-E-1 |
105A Support, Main Level |
Ceiling Heat Pump |
09/21L |
|
|
| 523-107-E-1 |
107 (Main Level) |
Ceiling Heat Pump |
09/27L |
|
|
| 523-109-E-1 |
109 (Main Level) |
Ceiling Heat Pump |
09/20Q |
|
|
| 523-109A-E-1 |
109A Support (Main Level) |
Ceiling Heat Pump |
09/20Q |
|
|
| 523-111-E-1 |
111, adjacent hall (Main Level) |
Ceiling Heat Pump |
09/10T |
|
|
| 523-113-E-1 |
113, adjacent hall (Main Level) |
Ceiling Heat Pump |
09/10Q |
|
|
| 523-113A-E-1 |
113A Support (Main Level) |
Ceiling Heat Pump |
09/10Q |
|
|
| 523-115-E-1 |
115 Team room (Main Level) |
Ceiling Heat Pump |
09/20T |
|
|
| 523-ERU2 |
103-113 Main level wing |
ERU |
09/17QT |
|
|
| 523-112-E-1 |
112 (Main Level) |
Ceiling Heat Pump |
09/20T |
|
|
| 523-114-E-1 |
114 (Main Level) |
Ceiling Heat Pump |
09/14J |
|
|
| 523-114-E-2 |
Matsunaga main hall by 114 |
Ceiling Heat Pump |
09/14J |
|
|
| 523-106-E-1 |
106 Music, 106A Music Office, hall by 106A |
Ceiling Heat Pump |
09/18Q |
|
|
| 523-116-E-1 |
116, Hall by 116, 108, 110 (Main Level), hall between 118 and 106 |
Ceiling Heat Pump |
09/18Q |
|
|
| 523-118-E-1 |
118 Dual Purpose Room |
Ceiling Heat Pump |
09/18Q |
|
|
| 523-120-E-1 |
120 Math |
Ceiling Heat Pump |
09/17J |
|
|
| 523-124-E-1 |
124, 122 Storage |
Ceiling Heat Pump |
09/14Q |
|
|
| 523-124-E-2 |
Matsunaga main hall by 124, 122 |
Ceiling Heat Pump |
09/14K |
|
|
| 523-Stage-E-1 |
MPR stage, 126A and 126C storage rooms |
Ceiling Heat Pump |
09/20SL |
|
|
| 523-126-E-1 |
126 Multi-Purpose Room, southmost unit (closest to Matsunaga main hall) |
Ceiling Heat Pump |
09/20SL |
|
|
| 523-126-E-2 |
126 Multi-Purpose Room, 2nd unit from south end |
Ceiling Heat Pump |
09/20SL |
|
|
| 523-126-E-3 |
126 Multi-Purpose Room, 3rd unit from south end |
Ceiling Heat Pump |
09/20SL |
|
|
| 523-126-E-4 |
126 Multi-Purpose Room, northmost unit (closest to Longview long hall) |
Ceiling Heat Pump |
09/20SL |
|
|
| 523-126D-E-1 |
126D Kitchen |
Ceiling Heat Pump |
09/14L |
|
|
| 523-132B-E-1 |
132B Kitchen storage |
Ceiling Heat Pump |
09/14L |
|
|
| 523-126F-E-1 |
126F BSM office, 126E Storage |
Ceiling Heat Pump |
09/14K |
|
|
| 523-ERU3 |
Multiple rooms |
ERU |
09/05SK |
|
|
| 523-ERU4 |
Multiple rooms |
ERU |
09/04QL |
|
|
| 523-130-E-1 |
130 |
Ceiling Heat Pump |
09/11L |
|
|
| 523-130-E-2 |
Hall by 130, Matsunaga main hall by 130, entrance vestibule |
Ceiling Heat Pump |
09/11L |
|
|
| 523-117-E-1 |
117, adjacent hall |
Ceiling Heat Pump |
09/10L |
|
|
| 523-119-E-1 |
119, adjacent hall |
Ceiling Heat Pump |
09/10J |
|
|
| 523-119A-E-1 |
119A Support |
Ceiling Heat Pump |
09/10T |
|
|
| 523-121-E-1 |
121 |
Ceiling Heat Pump |
09/10L |
|
|
| 523-123-E-1 |
123 |
Ceiling Heat Pump |
09/10K |
|
|
| 523-123A-E-1 |
123A Support |
Ceiling Heat Pump |
09/10J |
|
|
| 523-125-E-1 |
125, adjacent hall |
Ceiling Heat Pump |
09/10K |
|
|
| 523-127-E-1 |
127, adjacent hall |
Ceiling Heat Pump |
09/10S |
|
|
| 523-127A-E-1 |
127A Support |
Ceiling Heat Pump |
09/10S |
|
|
| 523-129-E-1 |
129 Team room |
Ceiling Heat Pump |
09/11J |
|
|
| 523-133-E-1 |
133 |
Ceiling Heat Pump |
09/11J |
|
|
| 523-ERU1 |
117-133 wing |
ERU |
09/17J |
|
|
| 523-MechRm-E-1 |
Lower level mechanical room |
Ceiling Heat Pump |
09/11J |
|
|
| 523-HU/Elevator-E-1 |
Mechanical rooms by elevator, hall |
Ceiling Heat Pump |
09/11L |
|
|
| 523-010-E-1 |
010, adjacent hall |
Ceiling Heat Pump |
09/12Q |
|
|
| 523-010A-E-1 |
010A Support |
Ceiling Heat Pump |
09/12Q |
|
|
| 523-011-E-1 |
011, adjacent hall |
Ceiling Heat Pump |
09/12Q |
|
|
| 523-012-E-1 |
012 |
Ceiling Heat Pump |
09/12Q |
|
|
| 523-012A-E-1 |
012A Support |
Ceiling Heat Pump |
09/13T |
|
|
| 523-013-E-1 |
013 |
Ceiling Heat Pump |
09/13T |
|
|
| 523-014-E-1 |
014, adjacent hall |
Ceiling Heat Pump |
09/13T |
|
|
| 523-014A-E-1 |
014A Support |
Ceiling Heat Pump |
09/13Q |
|
|
| 523-015-E-1 |
015, adjacent hall |
Ceiling Heat Pump |
09/13Q |
|
|
| 523-016-E-1 |
016 Team room |
Ceiling Heat Pump |
09/13Q |
|
|
| 523-LL/101-E-1 |
101 (Lower Level) |
Ceiling Heat Pump |
|
|
|
| 523-LL/102-E-1 |
102, adjacent hall (Lower Level) |
Ceiling Heat Pump |
|
|
|
| 523-LL/103-E-1 |
103 Flex (Lower Level) |
Ceiling Heat Pump |
09/13K |
|
|
| 523-LL/104-E-1 |
104 (Lower Level) |
Ceiling Heat Pump |
09/13K |
|
|
| 523-LL/105-E-1 |
105 (Lower Level) |
Ceiling Heat Pump |
09/13K |
|
|
| 523-LL/106-E-1 |
106 Flex (Lower Level) |
Ceiling Heat Pump |
09/21Q |
|
|
| 523-LL/107-E-1 |
107 (Lower Level) |
Ceiling Heat Pump |
09/13K |
|
|
| 523-LL/109-E-1 |
109 (Lower Level) |
Ceiling Heat Pump |
09/13J |
|
|
| 523-LL/110-E-1 |
110 Flex (Lower Level) |
Ceiling Heat Pump |
09/20Q |
|
|
| 523-LL/111-E-1 |
111 (Lower Level) |
Ceiling Heat Pump |
09/13J |
|
|
| 523-LL/112-E-1 |
112 (Lower Level) |
Ceiling Heat Pump |
09/13J |
|
|
| 523-LL/116-E-1 |
116 Support, 115 Therapy (Lower Level) |
Ceiling Heat Pump |
09/21Q |
|
|
| 523-ERU5 |
Multiple rooms |
ERU |
09/04SK |
|
|
| 523-ERU6 |
Multiple rooms |
ERU |
09/04QT |
|
|
|
Longview School |
Unit ID |
Area/Zone served by Unit |
Unit Type* |
Cleaned |
Mech Eval |
Repairs/Notes |
| 951-100-E-1 |
100 Office (Longview) |
Ceiling Heat Pump |
09/26J |
|
|
| 951-HU/100-E-1 |
Hall by Longview office |
Ceiling Heat Pump |
09/26J |
|
|
| 951-HU/100-E-2 |
Hall by Longview office, gym |
Ceiling Heat Pump |
09/26J |
|
|
| 951-HU/100F-E-1 |
100F Conference room, hall |
Ceiling Heat Pump |
|
|
|
| 951-HU/100G-E-1 |
100G Office |
Ceiling Heat Pump |
09/25J |
|
|
| 951-102G-E-1 |
102G IMC (Longview) |
Ceiling Heat Pump |
09/26J |
|
|
| 951-134-E-1 |
134 MPR (Longview) |
Ceiling Heat Pump |
09/24SK |
|
|
| 951-136-E-1 |
136 Speech/Language, hall by 134 and 136 |
Ceiling Heat Pump |
09/27L |
|
|
| 951-HU/137-E-1 |
Longview hall by 134, 137 |
Ceiling Heat Pump |
|
|
|
| 951-137-E-1 |
137 |
Ceiling Heat Pump |
09/24S |
|
|
| 951-138-E-1 |
138 OT/PT, adjacent storage room |
Ceiling Heat Pump |
09/25J |
|
|
| 951-140-E-1 |
140 Office |
Ceiling Heat Pump |
09/24S |
|
|
| 951-141-E-1 |
141 |
Ceiling Heat Pump |
09/24K |
|
|
| 951-143-E-1 |
143 |
Ceiling Heat Pump |
09/24K |
|
|
| 951-144-E-1 |
144 Art/Music, adjacent hall by 142/144 |
Ceiling Heat Pump |
09/25K |
|
|
| 951-HU/144-E-1 |
Hall by 144, hall between 144 and pool |
Ceiling Heat Pump |
09/25K |
|
|
| 951-145-E-1 |
145 |
Ceiling Heat Pump |
09/24L |
|
|
| 951-146-E-1 |
146 Equipment Repair |
Ceiling Heat Pump |
09/27L |
|
|
| 951-147-E-1 |
147 |
Ceiling Heat Pump |
09/24L |
|
|
| 951-149-E-1 |
149 |
Ceiling Heat Pump |
09/24J |
|
|
| 951-151-E-1 |
151 |
Ceiling Heat Pump |
09/24J |
|
|
| 951-152-E-1 |
152, 150, 148, hall by 152 |
Ceiling Heat Pump |
09/26J |
|
|
| 951-153-E-1 |
153 |
Ceiling Heat Pump |
09/24J |
|
|
| 951-154-E-1 |
154, hall by 154 |
Ceiling Heat Pump |
09/24L |
|
|
| 951-HVU2 |
157 Longview Gym , gym storage |
HVU |
09/06L |
|
|
| 951-PU1 |
Pool |
AHU |
09/04LJ |
|
|
| 951-HU/157-E-1 |
Hall by gym, 157A gym office |
Ceiling Heat Pump |
09/24Q |
|
|
| 951-HU/152G-E-1 |
Pool locker rooms |
Ceiling Heat Pump |
|
|
|
| 951-159-E-1 |
159 Art |
Ceiling Heat Pump |
09/24T |
|
|
| 951-160-E-1 |
160 |
Ceiling Heat Pump |
09/24T |
|
|
| 951-161-E-1 |
161 |
Ceiling Heat Pump |
09/24T |
|
|
| 951-163-E-1 |
163, hall, 162 |
Ceiling Heat Pump |
09/24Q |
|
|
| 951-164-E-1 |
164 |
Ceiling Heat Pump |
09/25J |
|
|
| 951-165-E-1 |
165 |
Ceiling Heat Pump |
09/24Q |
|
|
| * AHU: central air handling unit; HVU: central air handler providing heating and ventilation (outdoor air supply) only, no cooling; ERU: energy-recovery unit - central air handler that exhausts building air and provides cooled or heated outdoor air; Ceiling Unit Ventilator: ceiling-mounted ventilation unit; Unit Ventilator: wall-mounted ventilation unit; Ceiling Fan Coil Unit: ceiling-mounted ventilation unit (does not supply outdoor air); Fan Coil Unit: wall-mounted ventilation unit (does not supply outdoor air); RTU: rooftop air handler; VAV box: variable-air volume box (duct-mounted device that controls room temperatures by modulating airflow); Reheat Coil: duct-mounted device that provides supplemental heat. VAV boxes and reheat coils typically do not require cleaning; Heat Pump: Heat pump or refrigerant air-conditioner with electric heat; Ceiling Heat Pump: ceiling-mounted heat pump. |
Exhaust Fan PM (Mechanical Evaluation; Repairs, if needed):
Fan No. |
Area/Zone served by Unit |
Unit Type |
Mech Eval |
Repairs |
| |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Follow-Up Walkthrough:
Exit Meeting (Presentation of Site Visit Report and Building Maintenance Plan):
|
|