IAQ Team Building Maintenance Plan (BMP) Visit Progress - Beall ES (207) Initial Visit
Unit ID |
Area/Zone served by Unit |
Unit Type* |
Cleaned |
Mech Eval |
Repairs |
| 207-Gym-AHU |
Gym |
AHU |
03/14QTK |
07/31EJC |
|
| 207-GymOffice-E-1 |
Gym office |
Ceiling Univent |
01/24L |
03/07EJC |
Replaced thermostat. |
| 207-GymStorage-E-1 |
Gym storage room ceiling |
Ceiling Univent |
01/29SJ |
02/12EJC |
Fan motor replaced; thermostat replaced; water valve freed to allow proper flow to coil; installed new on/off switch. . |
| 207-SBR/Gym-E-1 |
Gym office restroom |
Ceiling Univent |
01/24J |
03/07EJC |
Replaced thermostat. |
| 207-BBR/Gym-E-1 |
Boys' restroom by gym |
Ceiling Univent |
12/20S |
01/30E |
Fan motor replaced. Thermostat replaced; new air lines installed. |
| 207-GBR/Gym-E-1 |
Girls' restroom by gym |
Ceiling Univent |
01/25S |
03/07EJC |
Fan motor requires replacement. Thermostat re-calibrated. |
| 207-HU/BoilerRoom-E-1 |
Hall by boiler room |
Ceiling Univent |
12/20J |
02/23EJC |
|
| 207-BBR/101-E-1 |
Boys' restroom by 101 |
Ceiling Univent |
12/19Q |
02/21EJC |
Installed new thermostat; installed new air lines to unit. |
| 207-BBR/101-A-1 |
Boys' restroom by 101 |
Fin-Tube Heater |
12/19Q |
02/21EJC |
|
| 207-GBR/101-E-1 |
Girls' restroom by 101 |
Ceiling Univent |
12/20L |
02/22EJC |
Replaced thermostat; installed new air lines and pressure switch. |
| 207-GBR/101-C-1 |
Girls' restroom by 101 |
Fin-Tube Heater |
12/20L |
02/22EJC |
|
| 207-101-B-1 |
101 |
Univent |
12/15S |
01/10J |
Thermostat re-calibrated; new air line to unit installed. |
| 207-102-D-1 |
102 |
Univent |
12/19J |
01/10J |
Thermostat re-calibrated; new air line to unit installed. |
| 207-103-B-1 |
103 |
Univent |
12/19S |
01/11C |
Thermostat re-calibrated; new air line to unit installed. |
| 207-104-D-1 |
104 |
Univent |
12/19L |
01/11J |
Thermostat re-calibrated; new air line to unit installed. |
| 207-105-B-1 |
105 |
Univent |
12/19Q |
01/11E |
Thermostat re-calibrated; new air line to unit installed; adjusted damper; replaced water valve top and spring assembly. |
| 207-106-D-1 |
106 |
Univent |
12/19T |
01/12J |
Thermostat re-calibrated; new air line to unit installed. |
| 207-106A-C-1 |
106A |
Electric Heater |
07/31T |
03/09EJC |
|
| 207-107-B-1 |
107 |
Univent |
01/02J |
02/28J |
Re-calibrated thermostat; installed new actuator, adjusted; installed new air line to unit. |
| 207-108-D-1 |
108 |
Univent |
01/02S |
01/12C |
Thermostat re-calibrated; new air line to unit installed; adjusted air damper and repaired actuator. |
| 207-109-B-1 |
109 |
Univent |
01/02Q |
01/12E |
Thermostat re-calibrated; new air line to unit installed. |
| 207-110-D-1 |
110 |
Univent |
01/02T |
01/16E |
Thermostat re-calibrated. |
| 207-HU/110-E-1 |
Hall by 110 |
Ceiling Univent |
01/17QT |
01/19E |
Thermostat replaced. |
| 207-111-B-1 |
111 |
Univent |
01/02L |
01/16C |
Thermostat re-calibrated. |
| 207-111A-D-1 |
111A |
Fin-Tube Heater |
01/17QT |
01/16C |
|
| 207-SBR/111A-C-1 |
Staff restroom "K" by 111A |
Fin-Tube Heater |
01/17QT |
01/16E |
|
| 207-SBR/111A-C-2 |
Staff restroom "J" by 111A |
Fin-Tube Heater |
01/17QT |
01/16C |
|
| 207-Kitchen-E-1 |
Kitchen |
Ceiling Univent |
01/25QT |
02/27J |
Fan motor needs replacement. Replaced thermostat; adjusted dampers. |
| 207-KitchenStorage-E-1 |
Kitchen storage room |
Ceiling Univent |
01/25QT |
03/09EJC |
Thermostat re-calibrated. |
| 207-HU/APR-E-1 |
Hall by APR |
Ceiling Univent |
01/18QT |
01/19C |
|
| 207-APR-RTU1 |
All-Purpose Room |
RTU #1 |
12/18LJ |
07/31EJC |
|
| 207-APRStorage-E-1 |
All-Purpose Room Storage Rm |
Univent |
01/29QT |
02/27C |
Thermostat re-calibrated. |
| |
|
|
|
|
|
| 207-APR-E-1 |
All-Purpose Room |
Ceiling Univent |
01/29SJ |
02/13JC |
Thermostat re-calibrated. |
| 207-APR-E-2 |
All-Purpose Room |
Ceiling Univent |
01/29QT |
02/13JC |
Thermostat re-calibrated. |
| 207-APR-E-3 |
All-Purpose Room |
Ceiling Univent |
07/31T |
02/27E |
Thermostat re-calibrated. |
| 207-APR-E-4 |
All-Purpose Room |
Ceiling Univent |
01/26QS |
02/26EC |
Thermostat re-calibrated. |
| 207-SBR/Lounge-E-1 |
Staff lounge |
Ceiling Univent |
01/19QT |
01/19J |
Thermostat re-calibrated. |
| 207-IMC-RTU3 |
IMC |
RTU #3 |
12/18QT |
07/31EJC |
|
| 207-IMC-C-1 |
IMC |
Univent |
01/12Q |
01/18C |
Thermostat re-calibrated; new air line to unit installed; adjusted damper. |
| 207-IMC-C-2 |
IMC |
Univent |
01/16T |
01/18E |
Thermostat re-calibrated; new air line to unit installed; re-wired electrical-pneumatic switch. |
| 207-IMC-C-3 |
IMC |
Univent |
01/16L |
01/18E |
Thermostat re-calibrated; new air line to unit installed; repaired stuck air damper; re-wired freezestat. |
| 207-IMCOffice-E-1 |
IMC office |
Ceiling Univent |
01/16J |
01/18C |
Thermostat re-calibrated; repaired fan motor; installed new motor switch. |
| 207-IMCStorage-E-1 |
IMC storage room |
Ceiling Univent |
01/16Q |
01/18J |
Thermostat re-calibrated. |
| 207-Studio-C-1 |
TV studio |
Fan Coil Unit |
01/12S |
01/18J |
Thermostat re-calibrated; new air line to unit installed; wired new electrical-pneumatic switch. |
| 207-MainEnt-D-1 |
Main entrance |
Univent |
01/23S |
02/28E |
Replaced thermostat; replaced air switching station. |
| 207-MainEnt-E-1 |
Main entrance |
Ceiling Univent |
01/22QT |
02/12EJC |
Thermostat replaced; fan motors oiled; new water valve top installed. |
| 207-MainOffice-RTU2 |
Main office |
RTU #2 |
12/18S |
07/31EJC |
|
| 207-MainOffice-A-1 |
Main office reception |
Fan Coil Unit |
01/22J |
01/30E |
Outdoor air intake filled in with concrete (wall repair?). Thermostat re-calibrated; on/off switch repaired; installed new pneumatic line to unit. |
| 207-MainOffice-A-2 |
Main office ast. principal's office |
Fan Coil Unit |
01/23T |
01/30E |
Thermostat re-calibrated. |
| 207-MainOffice-A-3 |
Main office conference |
Fan Coil Unit |
01/22S |
01/31J |
Thermostat re-calibrated. |
| 207-MainOffice-A-4 |
Main office principal's office |
Fan Coil Unit |
01/23L |
01/31C |
Thermostat re-calibrated. |
| 207-MainOffice-D-1 |
Main office principal's office |
Fan Coil Unit |
01/23Q |
01/30J |
Thermostat re-calibrated. |
| 207-MainOffice-D-2 |
Main office BSM office |
Fan Coil Unit |
07/31T |
01/30C |
Thermostat re-calibrated. |
| 207-MainOffice-D-3 |
Main office storage |
Fan Coil Unit |
01/23J |
02/28C |
Replaced fan motor; re-calibrated thermostat. |
| 207-MainOffice-D-4 |
Main office staff development |
Fan Coil Unit |
01/25LJ |
01/30J |
Thermostat re-calibrated. |
| 207-MainOffice-C-1 |
Main office work room |
Fan Coil Unit |
01/24Q |
01/30C |
Thermostat re-calibrated. |
| 207-MainOffice-E-1 |
Main office hall to work room |
Fan Coil Unit |
03/05Q |
02/22EJC |
Fan motor replaced; thermostat re-calibrated. |
| 207-HealthRm-E-1 |
Health room |
Ceiling Univent |
01/24T |
03/09EJC |
Thermostat re-calibrated. |
| 207-1-E-1 |
1 - Computer lab (North) |
Ceiling Univent |
01/10LJ |
01/29C |
Re-calibrated thermostat. |
| 207-1-E-2 |
1 - Computer lab (South) |
Ceiling Univent |
01/11L |
01/29E |
Re-calibrated thermostat. |
| 207-2-D-1 |
2 - Art |
Univent |
01/03L |
01/22J |
Replaced thermostat; adjusted dampers; repaired actuator; installed new pneumatic line for proper operation; replaced on/off switch. |
| 207-3-B-1 |
3 |
Univent |
01/03J |
01/22E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-4-D-1 |
4 |
Univent |
01/03S |
01/22C |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-5-B-1 |
5 |
Univent |
01/03T |
01/23J |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-6-D-1 |
6 |
Univent |
01/03Q |
01/23E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-7-E-1 |
7 |
Ceiling Univent |
01/04S |
01/29J |
Re-calibrated thermostat. |
| 207-8-D-1 |
8 - Counselor |
Univent |
01/04T |
01/23C |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-HU/8-E-1 |
Hall across 8 |
Ceiling Univent |
01/11Q |
02/20EJC |
Installed new thermostat; installed new valve top; installed new air lines. |
| 207-BBR/8-E-1 |
Boys' restroom "Q" across 8 |
Ceiling Univent |
01/10S |
01/26E |
Replaced thermostat; installed new pneumatic line; installed pressure switch. |
| 207-GBR/8-E-1 |
Girls' restroom "R" across 8 |
Ceiling Univent |
01/11S |
02/21EJC |
Fan motor replaced; new thermostat; new air lines to unit.. |
| 207-8A-D-1 |
8A |
Univent |
12/29J |
01/23EJC |
Re-calibrated thermostat; installed new pneumatic line for proper operation. |
| 207-9-B-1 |
9 |
Univent |
01/04Q |
01/23EJC |
Re-calibrated thermostat; installed new pneumatic line for proper operation. |
| 207-10-A-1 |
10 |
Univent |
12/28J |
01/24J |
Re-calibrated thermostat; adjusted damper; installed new pneumatic line for proper operation. |
| 207-10-A-2 |
10 storage |
Fin-Tube Heater |
12/28J |
01/24J |
|
| 207-10A-E-1 |
10A |
Ceiling Univent |
01/10Q |
01/25E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation; re-wired electrical-pneumatic switch. |
| 207-11-A-1 |
11 |
Univent |
01/04J |
01/25C |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-12-E-1 |
12 |
Ceiling Univent |
01/10Q |
01/25E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation; re-wired electric-pneumatic switch; re-mounted unit. |
| 207-13-B-1 |
13 |
Univent |
01/04L |
01/25C |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-14-D-1 |
14 |
Univent |
01/09J |
01/24E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-14-A-1 |
14 storage |
Fin-Tube Heater |
01/25L |
01/24E |
|
| 207-15-B-1 |
15 |
Univent |
01/08J |
01/26J |
Re-calibrated thermostat; re-wired freezestat; installed new pneumatic line to unit. |
| 207-16-D-1 |
16 |
Univent |
01/09L |
01/25J |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-17-C-1 |
17 |
Univent |
01/09Q |
01/26C |
Re-calibrated thermostat; installed new pneumatic line to unit. |
| 207-18-C-1 |
18 |
Univent |
01/09S |
01/24C |
Re-calibrated thermostat; adjusted damper; installed new pneumatic line for proper operation. |
| 207-18-C-2 |
18 closet |
Fin-Tube Heater |
01/25L |
01/24C |
|
| 207-HU/18-E-1 |
Pod Exterior Entrance Hall |
Ceiling Univent |
01/12LJ |
01/25J |
Replaced thermostat. |
| 207-IHC-A-1 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10C |
|
| 207-IHC-A-2 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10C |
|
| 207-IHC-A-3 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10C |
|
| 207-IHC-A-4 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10C |
|
| 207-IHC-A-5 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10J |
|
| 207-IHC-A-6 |
Intercorridor Connector |
Fin-Tube Heater |
01/17SLJ |
01/10J |
|
| 207-201-B-1 |
201 |
Univent |
12/07QT |
01/02E |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-HU/201-E-1 |
Hall by 201 |
Ceiling Univent |
12/12QJ |
01/10E |
Installed new thermostat. |
| 207-BBR/201-E-1 |
Boys' restroom by 201 |
Ceiling Univent |
12/15QT |
02/23EJC |
Replaced thermostat; installed new air lines and pressure control. |
| 207-GBR/201-E-1 |
Girls' restroom by 201 |
Ceiling Univent |
12/15QT |
02/23EJC |
Replaced thermostat; installed new air lines and pressure control. |
| 207-201A-A-1 |
201A |
Univent |
12/07LJ |
01/08E |
Re-calibrated thermostat . |
| 207-202-B-1 |
202 |
Univent |
12/06QT |
01/02C |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-203-B-1 |
203 |
Univent |
12/07QT |
01/02J |
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation. |
| 207-204-D-1 |
204 |
Univent |
12/06S |
01/08C |
Re-calibrated thermostat. |
| 207-205-B-1 |
205 |
Univent |
12/08T |
01/08E |
Re-calibrated thermostat. |
| 207-206-D-1 |
206 |
Univent |
12/08S |
01/08C |
Re-calibrated thermostat. |
| 207-207-B-1 |
207 |
Univent |
12/08Q |
01/08E |
Re-calibrated thermostat; replaced switch. |
| 207-208-D-1 |
208 |
Univent |
12/08S |
01/09E |
Thermostat re-calibrated; new air line to unit installed; switch replaced. |
| 207-209-B-1 |
209 |
Univent |
12/11T |
01/09J |
Thermostat re-calibrated; new air line to unit installed; dampers adjusted. |
| 207-210-D-1 |
210 |
Univent |
12/11S |
01/09J |
Thermostat re-calibrated; new air line to unit installed; dampers adjusted. |
| 207-211-B-1 |
211 |
Univent |
12/11Q |
01/09C |
Thermostat re-calibrated; new air line to unit installed. |
| 207-SBR/211A-C-1 |
Staff restroom "P" by 211A |
Fin-Tube Heater |
12/12QT |
03/07EJC |
|
| 207-SBR/211A-C-2 |
Staff restroom "O" by 211A |
Fin-Tube Heater |
12/12QT |
03/07EJC |
|
| 207-HU/211-E-1 |
Hall by 211A |
Ceiling Univent |
12/12QT |
01/10E |
|
| 207-211A-C-1 |
211A |
Fin-Tube Heater |
12/12QT |
01/10J |
|
| 207-MO043-C-1 |
Portable MO-043 (112 Music) |
Heat Pump |
12/13QT |
03/01EJC |
Adjusted air damper. |
| 207-MO043-C-2 |
Portable MO-043 (112 Music) |
Heat Pump |
12/13QT |
03/01EJC |
Adjusted air damper. |
| 207-ML477-D-1 |
Portable ML-477 (113) |
Heat Pump |
12/14Q |
03/09EJC |
Energy Mgmt controls thermostat. |
| 207-ML478-B-1 |
Portable ML-478 (114) |
Heat Pump |
12/14S |
03/01EJC |
|
| 207-ML479-B-1 |
Portable ML-479 (115) |
Heat Pump |
12/14J |
03/01EJC |
|
| 207-ML598-D-1 |
Portable ML-598 (116) |
Heat Pump |
12/13J |
03/01EJC |
|
| 207-ML597-D-1 |
Portable ML-597 (117) |
Heat Pump |
12/14Q |
03/01EJC |
|
* AHU: central air handling unit; Ceiling Univent: ceiling-mounted unit ventilator; Univent: wall-mounted unit ventilator; RTU: rooftop air handler |
Fan No. |
Area/Zone served by Unit |
Unit Type |
Mech Eval |
Repairs |
| EF-A-1 |
Health room restroom |
Ceiling Inline Fan |
12/26K |
Restored power to fan (tied to light switch). |
| EF-A-2 |
Main office staff restroom |
Ceiling Inline Fan |
12/19K |
|
| EF-B |
Room 14 restroom |
Ceiling Inline Fan |
12/26K |
|
| EF-C-1 |
Room 11, 13 restrooms |
Ceiling Inline Fan |
12/26K |
|
EF-C-2 |
Room 15, 17 restrooms |
Ceiling Inline Fan |
12/26K |
|
EF-C-3 |
Room 16, 18 restrooms |
Ceiling Inline Fan |
12/26K |
|
EF-C-4 |
Electric room across from stage |
Ceiling Inline Fan |
12/26K |
|
| EF-C-5 |
Room 201 electric closet |
Ceiling Inline Fan |
12/19K |
|
EF-C-6 |
Electric closet by room 8 |
Ceiling Inline Fan |
12/20K |
|
| EF-C-7 |
Electric closet across room 101 |
Ceiling Inline Fan |
01/10K |
Replaced fan motor. |
| EF-C-8 |
Room 10A |
Ceiling Inline Fan |
01/11K |
|
EF-C-9 |
Room 12 |
Ceiling Inline Fan |
01/11K |
|
| EF-1 |
Kitchen restroom, dry storage |
Roof Exhaust Fan |
03/28EJC |
Replaced fan motor. |
| EF-2 |
Bldg Svc locker room, storage, soda machine room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan motor. |
| EF-3 |
Stage |
Roof Exhaust Fan |
03/28EJC |
Replaced fan motor, lubricated motor. |
| EF-4 |
IMC |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-4A |
Kitchen |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-5 |
Main office |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-6 |
Comp lab rm 3, rm 5, rm 7, rm9 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-7 |
Rm 2 kiln hood, rm 4, rm 6 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-8 |
Intercorridor connector |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, replaced fan motor. |
| EF-9 |
Boys' and girls' restrooms by 8 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
EF-10 |
Room 11, 13, 15, 17 storage rooms |
Ceiling Inline Fan |
12/26K |
|
| EF-11 |
Rooms 14 and 16, storage rooms (10, 18) |
Ceiling Inline Fan |
12/26K |
|
| EF-12 |
Rooms 101 - 111 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-13 |
Boys' and girls' restrooms across 201, boys' and girls' restrooms across 101 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-14 |
201, 201A, 203, 205, 207, 209, 211, storage room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-15 |
206, back stairwell, 208, 210 |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-16 |
Staff restrooms across cafeteria |
Roof Exhaust Fan |
03/28EJC |
|
| EF-17 |
Electrical room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-18 |
Trash room |
Roof Exhaust Fan |
03/28EJC |
|
| EF-19 |
Hall by cafeteria, IMC work room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan motor. |
| EF-20 |
Boiler room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| EF-20-2 |
Boiler room |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
| PR-12 |
Boys' and girls' restrooms by gym |
Roof Exhaust Fan |
03/28EJC |
Replaced fan motor, replaced fan belt, replaced belt pulley. |
| Gym #1 |
Gym |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |
Gym #2 |
Gym |
Roof Exhaust Fan |
03/28EJC |
Replaced fan belt, lubricated motor. |