IAQ Team Building Maintenance Plan (BMP) Visit Progress - Beall ES (207) Initial Visit

Kick-Off Meeting: 08/24/06

Walkthrough: 09/18/06, 09/21/06

Work Plan Provided to School: 10/31/06 - Download

Supply Ventilation Unit PM (Cleaning; Mechanical Evaluation; Repairs, if needed):

Unit ID
Area/Zone served by Unit
Unit Type*
Cleaned
Mech Eval
Repairs
207-Gym-AHU Gym
AHU
03/14QTK
07/31EJC
 
207-GymOffice-E-1 Gym office
Ceiling Univent
01/24L
03/07EJC
Replaced thermostat.
207-GymStorage-E-1 Gym storage room ceiling
Ceiling Univent
01/29SJ
02/12EJC
Fan motor replaced; thermostat replaced; water valve freed to allow proper flow to coil; installed new on/off switch. .
207-SBR/Gym-E-1 Gym office restroom
Ceiling Univent
01/24J
03/07EJC
Replaced thermostat.
207-BBR/Gym-E-1 Boys' restroom by gym
Ceiling Univent
12/20S
01/30E
Fan motor replaced. Thermostat replaced; new air lines installed.
207-GBR/Gym-E-1 Girls' restroom by gym
Ceiling Univent
01/25S
03/07EJC
Fan motor requires replacement. Thermostat re-calibrated.
207-HU/BoilerRoom-E-1 Hall by boiler room
Ceiling Univent
12/20J
02/23EJC
 
207-BBR/101-E-1 Boys' restroom by 101
Ceiling Univent
12/19Q
02/21EJC
Installed new thermostat; installed new air lines to unit.
207-BBR/101-A-1 Boys' restroom by 101
Fin-Tube Heater
12/19Q
02/21EJC
 
207-GBR/101-E-1 Girls' restroom by 101
Ceiling Univent
12/20L
02/22EJC
Replaced thermostat; installed new air lines and pressure switch.
207-GBR/101-C-1 Girls' restroom by 101
Fin-Tube Heater
12/20L
02/22EJC
 
207-101-B-1 101
Univent
12/15S
01/10J
Thermostat re-calibrated; new air line to unit installed.
207-102-D-1 102
Univent
12/19J
01/10J
Thermostat re-calibrated; new air line to unit installed.
207-103-B-1 103
Univent
12/19S
01/11C
Thermostat re-calibrated; new air line to unit installed.
207-104-D-1 104
Univent
12/19L
01/11J
Thermostat re-calibrated; new air line to unit installed.
207-105-B-1 105
Univent
12/19Q
01/11E
Thermostat re-calibrated; new air line to unit installed; adjusted damper; replaced water valve top and spring assembly.
207-106-D-1 106
Univent
12/19T
01/12J
Thermostat re-calibrated; new air line to unit installed.
207-106A-C-1 106A
Electric Heater
07/31T
03/09EJC
 
207-107-B-1 107
Univent
01/02J
02/28J
Re-calibrated thermostat; installed new actuator, adjusted; installed new air line to unit.
207-108-D-1 108
Univent
01/02S
01/12C
Thermostat re-calibrated; new air line to unit installed; adjusted air damper and repaired actuator.
207-109-B-1 109
Univent
01/02Q
01/12E
Thermostat re-calibrated; new air line to unit installed.
207-110-D-1 110
Univent
01/02T
01/16E
Thermostat re-calibrated.
207-HU/110-E-1 Hall by 110
Ceiling Univent
01/17QT
01/19E
Thermostat replaced.
207-111-B-1 111
Univent
01/02L
01/16C
Thermostat re-calibrated.
207-111A-D-1 111A
Fin-Tube Heater
01/17QT
01/16C
 
207-SBR/111A-C-1 Staff restroom "K" by 111A
Fin-Tube Heater
01/17QT
01/16E
 
207-SBR/111A-C-2 Staff restroom "J" by 111A
Fin-Tube Heater
01/17QT
01/16C
 
207-Kitchen-E-1 Kitchen
Ceiling Univent
01/25QT
02/27J
Fan motor needs replacement. Replaced thermostat; adjusted dampers.
207-KitchenStorage-E-1 Kitchen storage room
Ceiling Univent
01/25QT
03/09EJC
Thermostat re-calibrated.
207-HU/APR-E-1 Hall by APR
Ceiling Univent
01/18QT
01/19C
 
207-APR-RTU1 All-Purpose Room
RTU #1
12/18LJ
07/31EJC
 
207-APRStorage-E-1 All-Purpose Room Storage Rm
Univent
01/29QT
02/27C
Thermostat re-calibrated.
   
 
207-APR-E-1 All-Purpose Room
Ceiling Univent
01/29SJ
02/13JC
Thermostat re-calibrated.
207-APR-E-2 All-Purpose Room
Ceiling Univent
01/29QT
02/13JC
Thermostat re-calibrated.
207-APR-E-3 All-Purpose Room
Ceiling Univent
07/31T
02/27E
Thermostat re-calibrated.
207-APR-E-4 All-Purpose Room
Ceiling Univent
01/26QS
02/26EC
Thermostat re-calibrated.
207-SBR/Lounge-E-1 Staff lounge
Ceiling Univent
01/19QT
01/19J
Thermostat re-calibrated.
207-IMC-RTU3 IMC
RTU #3
12/18QT
07/31EJC
 
207-IMC-C-1 IMC
Univent
01/12Q
01/18C
Thermostat re-calibrated; new air line to unit installed; adjusted damper.
207-IMC-C-2 IMC
Univent
01/16T
01/18E
Thermostat re-calibrated; new air line to unit installed; re-wired electrical-pneumatic switch.
207-IMC-C-3 IMC
Univent
01/16L
01/18E
Thermostat re-calibrated; new air line to unit installed; repaired stuck air damper; re-wired freezestat.
207-IMCOffice-E-1 IMC office
Ceiling Univent
01/16J
01/18C
Thermostat re-calibrated; repaired fan motor; installed new motor switch.
207-IMCStorage-E-1 IMC storage room
Ceiling Univent
01/16Q
01/18J
Thermostat re-calibrated.
207-Studio-C-1 TV studio
Fan Coil Unit
01/12S
01/18J
Thermostat re-calibrated; new air line to unit installed; wired new electrical-pneumatic switch.
207-MainEnt-D-1 Main entrance
Univent
01/23S
02/28E
Replaced thermostat; replaced air switching station.
207-MainEnt-E-1 Main entrance
Ceiling Univent
01/22QT
02/12EJC
Thermostat replaced; fan motors oiled; new water valve top installed.
207-MainOffice-RTU2 Main office
RTU #2
12/18S
07/31EJC
 
207-MainOffice-A-1 Main office reception
Fan Coil Unit
01/22J
01/30E
Outdoor air intake filled in with concrete (wall repair?). Thermostat re-calibrated; on/off switch repaired; installed new pneumatic line to unit.
207-MainOffice-A-2 Main office ast. principal's office
Fan Coil Unit
01/23T
01/30E
Thermostat re-calibrated.
207-MainOffice-A-3 Main office conference
Fan Coil Unit
01/22S
01/31J
Thermostat re-calibrated.
207-MainOffice-A-4 Main office principal's office
Fan Coil Unit
01/23L
01/31C
Thermostat re-calibrated.
207-MainOffice-D-1 Main office principal's office
Fan Coil Unit
01/23Q
01/30J
Thermostat re-calibrated.
207-MainOffice-D-2 Main office BSM office
Fan Coil Unit
07/31T
01/30C
Thermostat re-calibrated.
207-MainOffice-D-3 Main office storage
Fan Coil Unit
01/23J
02/28C
Replaced fan motor; re-calibrated thermostat.
207-MainOffice-D-4 Main office staff development
Fan Coil Unit
01/25LJ
01/30J
Thermostat re-calibrated.
207-MainOffice-C-1 Main office work room
Fan Coil Unit
01/24Q
01/30C
Thermostat re-calibrated.
207-MainOffice-E-1 Main office hall to work room
Fan Coil Unit
03/05Q
02/22EJC
Fan motor replaced; thermostat re-calibrated.
207-HealthRm-E-1 Health room
Ceiling Univent
01/24T
03/09EJC
Thermostat re-calibrated.
207-1-E-1 1 - Computer lab (North)
Ceiling Univent
01/10LJ
01/29C
Re-calibrated thermostat.
207-1-E-2 1 - Computer lab (South)
Ceiling Univent
01/11L
01/29E
Re-calibrated thermostat.
207-2-D-1 2 - Art
Univent
01/03L
01/22J
Replaced thermostat; adjusted dampers; repaired actuator; installed new pneumatic line for proper operation; replaced on/off switch.
207-3-B-1 3
Univent
01/03J
01/22E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-4-D-1 4
Univent
01/03S
01/22C
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-5-B-1 5
Univent
01/03T
01/23J
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-6-D-1 6
Univent
01/03Q
01/23E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-7-E-1 7
Ceiling Univent
01/04S
01/29J
Re-calibrated thermostat.
207-8-D-1 8 - Counselor
Univent
01/04T
01/23C
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-HU/8-E-1 Hall across 8
Ceiling Univent
01/11Q
02/20EJC
Installed new thermostat; installed new valve top; installed new air lines.
207-BBR/8-E-1 Boys' restroom "Q" across 8
Ceiling Univent
01/10S
01/26E
Replaced thermostat; installed new pneumatic line; installed pressure switch.
207-GBR/8-E-1 Girls' restroom "R" across 8
Ceiling Univent
01/11S
02/21EJC
Fan motor replaced; new thermostat; new air lines to unit..
207-8A-D-1 8A
Univent
12/29J
01/23EJC
Re-calibrated thermostat; installed new pneumatic line for proper operation.
207-9-B-1 9
Univent
01/04Q
01/23EJC
Re-calibrated thermostat; installed new pneumatic line for proper operation.
207-10-A-1 10
Univent
12/28J
01/24J
Re-calibrated thermostat; adjusted damper; installed new pneumatic line for proper operation.
207-10-A-2 10 storage
Fin-Tube Heater
12/28J
01/24J
 
207-10A-E-1 10A
Ceiling Univent
01/10Q
01/25E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation; re-wired electrical-pneumatic switch.
207-11-A-1 11
Univent
01/04J
01/25C
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-12-E-1 12
Ceiling Univent
01/10Q
01/25E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation; re-wired electric-pneumatic switch; re-mounted unit.
207-13-B-1 13
Univent
01/04L
01/25C
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-14-D-1 14
Univent
01/09J
01/24E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-14-A-1 14 storage
Fin-Tube Heater
01/25L
01/24E
 
207-15-B-1 15
Univent
01/08J
01/26J
Re-calibrated thermostat; re-wired freezestat; installed new pneumatic line to unit.
207-16-D-1 16
Univent
01/09L
01/25J
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-17-C-1 17
Univent
01/09Q
01/26C
Re-calibrated thermostat; installed new pneumatic line to unit.
207-18-C-1 18
Univent
01/09S
01/24C
Re-calibrated thermostat; adjusted damper; installed new pneumatic line for proper operation.
207-18-C-2 18 closet
Fin-Tube Heater
01/25L
01/24C
 
207-HU/18-E-1 Pod Exterior Entrance Hall
Ceiling Univent
01/12LJ
01/25J
Replaced thermostat.
207-IHC-A-1 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10C
 
207-IHC-A-2 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10C
 
207-IHC-A-3 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10C
 
207-IHC-A-4 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10C
 
207-IHC-A-5 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10J
 
207-IHC-A-6 Intercorridor Connector
Fin-Tube Heater
01/17SLJ
01/10J
 
207-201-B-1 201
Univent
12/07QT
01/02E
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-HU/201-E-1 Hall by 201
Ceiling Univent
12/12QJ
01/10E
Installed new thermostat.
207-BBR/201-E-1 Boys' restroom by 201
Ceiling Univent
12/15QT
02/23EJC
Replaced thermostat; installed new air lines and pressure control.
207-GBR/201-E-1 Girls' restroom by 201
Ceiling Univent
12/15QT
02/23EJC
Replaced thermostat; installed new air lines and pressure control.
207-201A-A-1 201A
Univent
12/07LJ
01/08E
Re-calibrated thermostat .
207-202-B-1 202
Univent
12/06QT
01/02C
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-203-B-1 203
Univent
12/07QT
01/02J
Re-calibrated thermostat; adjusted dampers; installed new pneumatic line for proper operation.
207-204-D-1 204
Univent
12/06S
01/08C
Re-calibrated thermostat.
207-205-B-1 205
Univent
12/08T
01/08E
Re-calibrated thermostat.
207-206-D-1 206
Univent
12/08S
01/08C
Re-calibrated thermostat.
207-207-B-1 207
Univent
12/08Q
01/08E
Re-calibrated thermostat; replaced switch.
207-208-D-1 208
Univent
12/08S
01/09E
Thermostat re-calibrated; new air line to unit installed; switch replaced.
207-209-B-1 209
Univent
12/11T
01/09J
Thermostat re-calibrated; new air line to unit installed; dampers adjusted.
207-210-D-1 210
Univent
12/11S
01/09J
Thermostat re-calibrated; new air line to unit installed; dampers adjusted.
207-211-B-1 211
Univent
12/11Q
01/09C
Thermostat re-calibrated; new air line to unit installed.
207-SBR/211A-C-1 Staff restroom "P" by 211A
Fin-Tube Heater
12/12QT
03/07EJC
 
207-SBR/211A-C-2 Staff restroom "O" by 211A
Fin-Tube Heater
12/12QT
03/07EJC
 
207-HU/211-E-1 Hall by 211A
Ceiling Univent
12/12QT
01/10E
 
207-211A-C-1 211A
Fin-Tube Heater
12/12QT
01/10J
 
207-MO043-C-1 Portable MO-043 (112 Music)
Heat Pump
12/13QT
03/01EJC
Adjusted air damper.
207-MO043-C-2 Portable MO-043 (112 Music)
Heat Pump
12/13QT
03/01EJC
Adjusted air damper.
207-ML477-D-1 Portable ML-477 (113)
Heat Pump
12/14Q
03/09EJC
Energy Mgmt controls thermostat.
207-ML478-B-1 Portable ML-478 (114)
Heat Pump
12/14S
03/01EJC
 
207-ML479-B-1 Portable ML-479 (115)
Heat Pump
12/14J
03/01EJC
 
207-ML598-D-1 Portable ML-598 (116)
Heat Pump
12/13J
03/01EJC
 
207-ML597-D-1 Portable ML-597 (117)
Heat Pump
12/14Q
03/01EJC
 
* AHU: central air handling unit; Ceiling Univent: ceiling-mounted unit ventilator; Univent: wall-mounted unit ventilator; RTU: rooftop air handler

 

Exhaust Fan PM (Mechanical Evaluation; Repairs, if needed):

Fan No.
Area/Zone served by Unit
Unit Type
Mech Eval
Repairs
EF-A-1 Health room restroom
Ceiling Inline Fan
12/26K
Restored power to fan (tied to light switch).
EF-A-2 Main office staff restroom
Ceiling Inline Fan
12/19K
 
EF-B Room 14 restroom
Ceiling Inline Fan
12/26K
 
EF-C-1 Room 11, 13 restrooms
Ceiling Inline Fan
12/26K
 
EF-C-2
Room 15, 17 restrooms
Ceiling Inline Fan
12/26K
 
EF-C-3
Room 16, 18 restrooms
Ceiling Inline Fan
12/26K
 
EF-C-4
Electric room across from stage
Ceiling Inline Fan
12/26K
 
EF-C-5 Room 201 electric closet
Ceiling Inline Fan
12/19K
 
EF-C-6
Electric closet by room 8
Ceiling Inline Fan
12/20K
 
EF-C-7 Electric closet across room 101
Ceiling Inline Fan
01/10K
Replaced fan motor.
EF-C-8 Room 10A
Ceiling Inline Fan
01/11K
 
EF-C-9
Room 12
Ceiling Inline Fan
01/11K
 
EF-1 Kitchen restroom, dry storage
Roof Exhaust Fan
03/28EJC
Replaced fan motor.
EF-2 Bldg Svc locker room, storage, soda machine room
Roof Exhaust Fan
03/28EJC
Replaced fan motor.
EF-3 Stage
Roof Exhaust Fan
03/28EJC
Replaced fan motor, lubricated motor.
EF-4 IMC
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-4A Kitchen
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-5 Main office
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-6 Comp lab rm 3, rm 5, rm 7, rm9
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-7 Rm 2 kiln hood, rm 4, rm 6
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-8 Intercorridor connector
Roof Exhaust Fan
03/28EJC
Replaced fan belt, replaced fan motor.
EF-9 Boys' and girls' restrooms by 8
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-10
Room 11, 13, 15, 17 storage rooms
Ceiling Inline Fan
12/26K
 
EF-11 Rooms 14 and 16, storage rooms (10, 18)
Ceiling Inline Fan
12/26K
 
EF-12 Rooms 101 - 111
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-13 Boys' and girls' restrooms across 201, boys' and girls' restrooms across 101
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-14 201, 201A, 203, 205, 207, 209, 211, storage room
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-15 206, back stairwell, 208, 210
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-16 Staff restrooms across cafeteria
Roof Exhaust Fan
03/28EJC
 
EF-17 Electrical room
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-18 Trash room
Roof Exhaust Fan
03/28EJC
 
EF-19 Hall by cafeteria, IMC work room
Roof Exhaust Fan
03/28EJC
Replaced fan motor.
EF-20 Boiler room
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
EF-20-2 Boiler room
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
PR-12 Boys' and girls' restrooms by gym
Roof Exhaust Fan
03/28EJC
Replaced fan motor, replaced fan belt, replaced belt pulley.
Gym #1 Gym
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.
Gym #2
Gym
Roof Exhaust Fan
03/28EJC
Replaced fan belt, lubricated motor.

 

Air Station PM: 03/06J (cleaned condensor, changed oil for both compressors, changed filter)

 

Follow-Up Walkthrough:

 

Exit Meeting (Presentation of Site Visit Report and Building Maintenance Plan):

 

 

Notes:
 
 
 

 

 
     
     
     
  Updated May 9, 2011 | Maintained by Division of Maintenance ITSS  
     
  MCPS HOME | PARENTS | STUDENTS | STAFF | ABOUT | SCHOOLS | COMMUNITY | BACK TO TOP  
  ©1995–2007 Montgomery County Public Schools, 850 Hungerford Drive, Rockville, Maryland 20850  
  Contact | Privacy | Nondiscrimination/ADA | Get Acrobat | Get RealPlayer | Montgomery County
HOME | PARENTS | STUDENTS | STAFF | ABOUT | SCHOOLS | COMMUNITY | BOARD OF ED | TOP up arrow
©1995–2011 Montgomery County Public Schools, 850 Hungerford Drive, Rockville, Maryland 20850
Contact | Privacy | Nondiscrimination/ADA | Get Acrobat | Get Flash | Montgomery County